Problem | Possible Cause | Solution |
---|---|---|
The inverter’s KEDs and display are blank and the inverter does not operate in sufficient sunlight | Utility service panel AC and DC breakers are switched off | Turn on the breakers in the sequence described in “commissioning procedure”. |
The display reads inverter offline and ZC voltage fault | Utility service panel breakers are switched off. AC grid voltage is not present or incorrect | Turn on utility panel breakers. Check AC connections at the inverter’s terminals. Ensure AC voltage is within the range specified and “output” below is present |
The display reads inverter offline with sufficient sunlight | DC breakers are switched off (if installed), or DC fuses are blown (if installed). DC array voltage is not present | Turn on any DC breakers and check any DC fuses. Check DC connections at the inverter’s positive and negative DC terminals. Check for incorrectly wired PV arrays |
The display reads inverter offline and DC voltage fault with sufficient sunlight | DC voltage is present but incorrect | Check DC connections at the inverter’s positive and negative DC terminals. Check for incorrectly wired PV arrays. Ensure a voltage within the operating voltage range is present at the inverter’s terminals |
Only the inverter RED LED is illuminated and the display reads ground fault | Ground fault condition detected on the PV array | The PV system should be checked by a qualified electrician and repaired. See “PV ground fault detection” on page viii. To reconnect: 1. Make sure the GT inverter is not outputting power, and then switch off the DC breaker. If a DC breaker is not used, then disconnect the DC input. 2. Switch off the AC breaker 3. Remedy the actual ground fault Restart the unit using the sequence described in “commissioning procedure” below. |
The system value (power being produced by the system) displayed on each inverter’s LCD is different on inverters connected to the same daisy-chained network | Inverters can display different system values when one of the inverters is set to a different baud rate than the rest. That particular inverter’s baud rate screen show Tx and / or RX error | Check each inverter’s baud rate and compare the settings. Change any inverters with an incorrect baud rate. Make sure to follow the recommended procedure supplied by Xantrex grid tie solar inverter baud rate change procedure (976-0216-01-01 available on www.xantrex.com) |
To start the GT inverter |
---|
1. Ensure the AC breaker is off |
2. Ensure the correct multi-contact PV connectors are firmly plugged into the GT inverter as described in “connecting the DC wiring” on page 3-2 of the Xantrex solar inverter manual |
3. (GT 2.8-AU only) Ensure the AC quick connect is firmly inserted into the GT inverter and that the coupling ring is tight |
4. Uncover the PV array and/or close the main DC disconnect switch, if one is installed. Ensure the PV array is producing the required output voltage |
5. Connect the utility grid voltage by switching the AC circuit breaker on |
GT 2.8-AU | GT5.0-AU | |
---|---|---|
Maximum output power | 2800 W ac | 5000 W ac |
Maximum output current | 14.0 A | 24.0 A |
Nominal grid voltage | 230 Vac | |
Nominal grid frequency | 50 Hz | |
Total Harmonic Distortion (THD) | <3% | |
Power Factor | >0.99% (at rated power) >0.95% (full power range) |
Output Characteristics | Current Source | |
Output Current Waveform | Sine Wave |
Goodhew Electrical and Solar offers maintenance and servicing for all inverters and solar systems. Contact our team today for more information.
Goodhew Electrical and Solar is one of Brisbane, South East Queensland and Northern NSW’s longest standing and most popular solar companies. At Goodhew Electrical and Solar we endeavour to encompass the entire package.
Main service areas – Queensland (QLD) and Northern NSW – Brisbane, Cleveland, Bayside, Redlands, Logan City, Gold Coast, Tweed Heads.
Copyright © 2024 Goodhew Electrical & Solar. All Rights Reserved | Terms & Conditions | Privacy Policy